以光伏为代表的逆变型分布式电源(IIDG)以T接方式并网导致配电网中原有距离保护装置存在不正确动作风险,据此,提出一种适用于IIDG-T接的配电线路自适应距离保护原理。首先,结合IIDG故障输出特性分析IIDG-T接的配电网中传统距离保护误动、拒动原因;其次,基于故障等值网络探究IIDG-T接的配电线路故障电气量的演变规律;最后,针对三相短路和两相相间短路两类故障场景构建了完备的自适应距离保护方案。仿真结果表明,所提方案仅需依托本地量测信息即可自适应调整定值,可降低配电网通信成本,同时所提方案不受IIDG-T接容量、出力波动、故障位置及类型的干扰,在IIDG-T接的有源配电网场景中具有良好的适用性。
Abstract
The inverter-type distributed generation (IIDG) represented by photovoltaics is connected to the grid by T-connection, which leads to the risk of incorrect operation of the original distance protection device in the distribution network. Based on this, an adaptive distance protection principle for distribution lines suitable for IIDG-T connection is proposed. Firstly, combined with the output characteristics of IIDG fault, the causes of misoperation and rejection of traditional distance protection in IIDG-T connected distribution network are analyzed. Secondly, based on the fault equivalent network, the evolution law of the fault electrical quantity of the distribution line with IIDG-T connection is explored. Finally, a complete adaptive distance protection scheme is constructed for three-phase short-circuit and two-phase short-circuit fault scenarios. The simulation results show that the proposed scheme can adaptively adjust the setting value only by relying on the local measurement information, which can reduce the communication cost of the distribution network. At the same time, the proposed scheme is not disturbed by the IIDG-T connection capacity, output fluctuation, fault location and type, and has good applicability in the IIDG-T connected active distribution network scenario.
关键词
分布式电源 /
配电网 /
继电保护 /
T接分支 /
距离保护 /
自适应整定
Key words
distributed power supply /
distribution networks /
relay protection /
T-connected branch /
distance protection /
adaptive setting
{{custom_sec.title}}
{{custom_sec.title}}
{{custom_sec.content}}
参考文献
[1] 刘科研, 盛万兴, 马晓晨, 等. 基于多种群遗传算法的分布式光伏接入配电网规划研究[J]. 太阳能学报, 2021, 42(6): 146-155.
Liu K Y, Sheng W X, Ma X C, et al.Planning research of distributed photovoltaic source access distribution network based on multi-population genetic algorithm[J]. Acta Energiae Solaris Sinica, 2021, 42(6): 146-155.
[2] 魏东辉, 于舜尧, 房俊龙. 基于综合序电流的含光伏电源配电网纵联保护方案[J]. 太阳能学报, 2021, 42(7): 185-192.
Wei D H, Yu S Y, Fang J L.Pilot protection scheme based on integrated sequence current for distribution metwork with photovoltatic[J]. Acta Energiae Solaris Sinica, 2021, 42(7): 185-192.
[3] 王海云, 于希娟, 张雨璇, 等. 大型城市电网下分布式光伏承载力评估分析[J]. 太阳能学报, 2023, 44(6): 260-264.
Wang H Y, Yu X J, Zhang Y X, et al.Evaluation and analysis of distributed photovoltaic carrying capacity in large urban power grid[J]. Acta Energiae Solaris Sinica, 2023, 44(6): 260-264.
[4] 李海锋, 张正刚, 梁远升, 等. 基于谐波信号注入的含逆变型分布式电源配电网电流差动保护[J]. 电力系统自动化, 2023, 47(22): 120-128.
Li H F, Zhang Z G, Liang Y S, et al.Current differential protection for distribution network with inverter-interfaced distributed generators based on injection of harmonic signal[J]. Automation of Electric Power Systems, 2023, 47(22): 120-128.
[5] 戴志辉, 何静远, 王文卓, 等. 适用于逆变型分布式电源T 接的配电网线路纵联保护方案[J]. 电力自动化设备, 2024, 44(5): 88-94, 119.
Dai Z H, He J Y, Wang W Z, et al.Line pilot protection scheme for distribution network with inverter-interfaced distributed generation in T-connection mode[J]. Electric Power Automation Equipment, 2024, 44(5): 88-94, 119.
[6] 明潇宇, 吕飞鹏, 余晓, 等. 含T接逆变型分布式电源配电网的纵联保护方案[J]. 电测与仪表, 2020, 57(11): 74-79.
Ming X Y, Lyu F P, Yu X, et al.Pilot protection scheme for distribution network with T-connected inverter interfaced distributed generation[J]. Electrical Measurement & Instrumentation, 2020, 57(11): 74-79.
[7] 刘幸蔚, 李永丽, 陈晓龙, 等. 逆变型分布式电源T接线路后纵联差动保护的改进方案[J]. 电网技术, 2016, 40(4): 1257-1264.
Liu X W, Li Y L, Chen X L, et al.An improved scheme of longitudinal differential protection for teed lines with inverter-based distributed generations[J]. Power System Technology, 2016, 40(4): 1257-1264.
[8] 袁智勇, 徐全, 徐刚, 等. 含大容量分布式电源接入的配电网电流保护优化方案[J]. 电网技术, 2021, 45(5): 1862-1868.
Yuan Z Y, Xu Q, Xu G, et al.Current protection optimization scheme in distribution network with large capacity distributed generators[J]. Power System Technology, 2021, 45(5): 1862-1868.
[9] 余磊, 贾科, 温志文, 等. 计及量测数据丢失的主动配电网电流保护自适应整定方法[J]. 电力系统自动化, 2022, 46(15): 145-152.
Yu L, Jia K, Wen Z W, et al.Adaptive setting method of over current protection in active distribution network considering measurement data missing[J]. Automation of Electric Power Systems, 2022, 46(15): 145-152.
[10] Hunter L C, Booth C D, Egea-Alvarez A, et al.A new fast-acting backup protection strategy for embedded MVDC links in future distribution networks[J]. IEEE Transactions on Power Delivery, 2021, 36(2): 861-869.
[11] Liang Y Y, Li W L, Zha W T.Adaptive mho characteristic-based distance protection for lines emanating from photovoltaic power plants under unbalanced faults[J]. IEEE Systems Journal, 2021, 15(3): 3506-3516.
[12] 李桓. 含高密度逆变型分布式电源的配电网故障电流分析与抑制方法研究[D]. 淄博: 山东理工大学, 2020.
Li H.Research on fault current analysis and suppression of distribution system with high-density inverter-interfaced distributed generations[D]. Zibo: Shandong University of Technology, 2020.
[13] 罗竟哲. 含逆变型分布式电源配电网的纵联保护原理研究[D]. 广州: 华南理工大学, 2022.
Luo J Z.Research on pilot-protection principles for distribution networks with inverter-interfaced distributed generators[D]. Guangzhou: South China University of Technology, 2022.
[14] 邹南. 含逆变型分布式电源配电网单相断线故障分析与保护研究[D]. 北京: 华北电力大学, 2022.
Zou N.Analysis and protection research of single-phase disconnection fault for distribution network with inverter interfaced distributed generations[D]. Beijing: North China Electric Power University, 2022.
[15] 晁晨栩, 郑晓冬, 邰能灵, 等. 针对新能源场站送出线两相短路的负序阻抗重构距离保护[J]. 电力系统自动化, 2023, 47(22): 101-109.
Chao C X, Zheng X D, Tai N L, et al.Distance protection based on negative-sequence impedance reconstruction for phase-to-phase short circuit of renewable power plant transmission lines[J]. Automation of Electric Power Systems, 2023, 47(22): 101-109.
[16] 赵建文, 张鸿波, 胡雨佳. 含T接逆变型分布式电源配电网的自适应距离保护[J]. 可再生能源, 2024, 42(1): 64-70.
Zhao J W, Zhang H B, Hu Y J.Adaptive distance protection for distributed generation distribution network with T-connected inverter interfaced distributed generation[J]. Renewable Energy Resources, 2024, 42(1): 64-70.
[17] 戴志辉, 柳梅元, 韦舒清, 等. 基于超导磁储能的光伏场站送出线路距离保护[J]. 中国电力, 2024, 57(10): 102-114.
Dai Z H, Liu M Y, Wei S Q, et al.Distance protection for outgoing line of photovoltaic station based on superconducting magnetic energy storage[J]. Electric Power, 2024, 57(10): 102-114.
[18] 晁晨栩, 郑晓冬, 高飘, 等. 针对光伏场站送出线路不对称短路故障的自适应距离保护原理[J]. 中国电机工程学报, 2022, 42(18): 6681-6692.
Chao C X, Zheng X D, Gao P, et al.Adaptive distance protection for transmission line of photovoltaic station during asymmetric short circuit[J]. Proceedings of the CSEE, 2022, 42(18): 6681-6692.
[19] Xu K H, Zhang Z, Lai Q H, et al.Fault phase selection method applied to tie line of renewable energy power stations[J]. IET Generation, Transmission & Distribution, 2020, 14(13): 2549-2557.
基金
国家电网公司总部科技基金资助项目(5400-202340556A-3-2-ZN)