RESEARCH ON UNIFIED ACTIVE DAMPER APPLIED TO HARMONIC AMPLIFICATION CONTROL

Li Fei, Liu Mengtao, Zhang Xing, Ma Mingyao

Acta Energiae Solaris Sinica ›› 2022, Vol. 43 ›› Issue (10) : 518-523.

PDF(4256 KB)
Welcome to visit Acta Energiae Solaris Sinica, Today is
PDF(4256 KB)
Acta Energiae Solaris Sinica ›› 2022, Vol. 43 ›› Issue (10) : 518-523. DOI: 10.19912/j.0254-0096.tynxb.2021-0323

RESEARCH ON UNIFIED ACTIVE DAMPER APPLIED TO HARMONIC AMPLIFICATION CONTROL

  • Li Fei, Liu Mengtao, Zhang Xing, Ma Mingyao
Author information +
History +

Abstract

In the high permeability grid environment, the multi-inverter grid-connected system is more prone to harmonic amplification or even instability. Many scholars are committed to alleviating this problem by parallel active damper, but it is not easy to realize the virtual of small impedance and can not effectively suppress the amplification of grid background noise. In view of the above shortcomings, a unified active damper is proposed to make up for the shortcomings of the parallel active damper. Firstly, based on the impedance model, the harmonic amplification mechanism of the electrical network coupling system of multi-inverter under weak network is analyzed, and the reasons of the harmonic amplification and even instability of the system, the harmonic source of the system and underdamping characteristics is clarified. Secondly, the mechanism and shortcomings of parallel impedance damper to solve the above problems are introduced. Thirdly, a unified active damper combining series-parallel impedance in the virtual harmonic segment of the grid-connected point is proposed to solve the problem of harmonic amplification of the system and to improve the quality of the grid-connected current. Finally, RT-LAB HIL simulation platform is built to verify the effectiveness of the proposed scheme.

Cite this article

Download Citations
Li Fei, Liu Mengtao, Zhang Xing, Ma Mingyao. RESEARCH ON UNIFIED ACTIVE DAMPER APPLIED TO HARMONIC AMPLIFICATION CONTROL[J]. Acta Energiae Solaris Sinica. 2022, 43(10): 518-523 https://doi.org/10.19912/j.0254-0096.tynxb.2021-0323

References

[1] 张兴, 余畅舟, 刘芳, 等. 光伏并网多逆变器并联建模及谐振分析[J]. 中国电机工程学报, 2014, 34(3):336-345.
ZHANG X, YU C Z, LIU F, et al.Modeling and resonance analysis of multi-paralleled grid-tied converters in PV systems[J]. Proceedings of the CSEE, 2014, 34(3): 336-345.
[2] WANG X F, BLAABJERG F, CHEN Z.Synthesis of variable harmonic impedance in inverter-interfaced distributed generation unit for harmonic damping throughout a distribution network[J]. IEEE transactions on industry applications, 2012, 48(4): 1407-1417.
[3] WANG X F, BLAABJERG F, LISERRE M, et al.An active damper for stabilizing power-electronics-based AC systems[J]. IEEE transactions on power electronics, 2013, 29(7): 3318-3329.
[4] MING J, WANG Y B, WANG F, et al.Large-signal stability analysis and shunt active damper compensation for DC microgrid with multiple constant power loads[C]//2019 22nd International Conference on Electrical Machines and Systems (ICEMS), Harbin, China, 2019: 1-6.
[5] 张劲松, 段文燕, 孙孝峰, 等. 基于长传输线的并网系统谐波谐振抑制策略研究[J]. 太阳能学报, 2019, 40(9): 2561-2570.
ZHANG J S, DUAN W Y, SUN X F, et al.Research on harmonic resonance suppression strategy of grid-connected system based on long transmission line[J]. Acta energiae solaris sinica, 2019, 40(9): 2561-2570.
[6] 周文翔, 张兴, 李飞, 等. 基于电压型阻抗适配器的谐振抑制策略[J]. 电力电子技术, 2019, 53(5): 9-12.
ZHOU W X, ZHANG X, LI F, et al.Resonant suppression strategy based on voltage type impedance adapter[J]. Power electronics technology, 2019, 53(5): 9-12.
[7] WANG X F, PANG Y, LOH P C, et al.A series-LC-filtered active damper with grid disturbance rejection for AC power-electronics-based power systems[J]. IEEE transactions on power electronics, 2015, 30(8): 4037-4041.
[8] BAI H, WANG X F, BLAABJERG F.Passivity enhancement by series LC filtered active damper with zero current reference[C]//2016 IEEE 8th International Power Electronics and Motion Control Conference(IPEMC), Hefei, China, 2016: 2937-2944.
[9] BAI H F, WANG X F, LOH P C, et al.Passivity enhancement of grid-tied converters by series LC-filtered active damper[J]. IEEE transactions on industrial electronics, 2017, 64(1): 369-379.
[10] LIN Z H, RUAN X B.A three-phase adaptive active damper for improving the stability of grid-connected inverters under weak grid[C]//2019 IEEE Applied Power Electronics Conference and Exposition(APEC), Anaheim, CA, USA, 2019: 1084-1089.
[11] CHENG L, LIU Z, LIU J J, et al.An RL-type active damper for stabilizing wide band oscillations in grid-tied inverter systems[C]//2020 IEEE Energy Conversion Congress and Exposition (ECCE), Detroit, MI, USA, 2020: 1686-1693.