RESEARCH ON IMPACT OF OUTER POWER LOOP ONSTABILITY OF GRID-CONNECTED DFIG

  • Ma Songtao1, Xu Wenjia1, Xiang Zutao1, Gao Zhixuan1, Zhou Yunbin2, Sha Licheng2
Author information +
History +

Abstract

The outer-loop control is often ignored when using impedance method to solve the stability problem of the grid-connected doubly fed induction generator (DFIG) system. However, the influence of ignoring the outer-loop control on the stability of the system has not been deeply studied. To solve this problem, firstly, this paper proposes a broadband frequency admittance model of DFIG which includes both stator- rotor side converter (RSC) and grid side converter (GSC) with integrated power outer-loop controls. The accuracy and validity of the proposed admittance model are verified by electromagnetic transient simulation model. Secondly, based on the actual operational parameter ranges provided by wind turbine manufacturer, influence of variations in outer-loop control parameters on the admittance characteristics of DFIG is analyzed theoretically. The results demonstrate that variations in proportional coefficients significantly affect the admittance characteristics of DFIG. Further studies indicate that overlooking RSC outer-loop control may hinder the recognition of oscillation problems when using the impedance method in the grid-connected DFIG system across various frequency bands. This may lead to erroneous assessment of an actually oscillatory system as stable system, thereby posing a risk to the safe operation of the power system. Next, a practical example of grid-connected DFIG wind farm is established, and the impact of RSC outer-loop control parameters on oscillation stability is observed by the variation of RSC outer-loop control parameters, which validates the crucial role of incorporating the power outer-loop when impedance analysis is applied for oscillation stability assessment of grid-connected DFIG system.

Key words

doubly fed induction generator / admittance / stability / vector control / Nyquist diagrams / outer power loop

Cite this article

Download Citations
Ma Songtao, Xu Wenjia, Xiang Zutao, Gao Zhixuan, Zhou Yunbin, Sha Licheng. RESEARCH ON IMPACT OF OUTER POWER LOOP ONSTABILITY OF GRID-CONNECTED DFIG[J]. Acta Energiae Solaris Sinica. 2026, 47(4): 307-319 https://doi.org/10.19912/j.0254-0096.tynxb.2024-2168

References

[1] 狄依容, 甄永赞, 胡永强. 双馈风电场抑制次同步振荡的自适应增强阻尼控制方法[J]. 太阳能学报, 2024, 45(8): 603-612.
DI Y R, ZHEN Y Z, HU Y Q.Adaptive enhanced damping control method for double-fed wind farm restraing sub-synchronous oscillations[J]. Acta energiae solaris sinica, 2024, 45(8): 603-612.
[2] 李明节, 于钊, 许涛, 等. 新能源并网系统引发的复杂振荡问题及其对策研究[J]. 电网技术, 2017, 41(4): 1035-1042.
LI M J, YU Z, XU T, et al.Study of complex oscillation caused by renewable energy integration and its solution[J]. Power system technology, 2017, 41(4): 1035-1042.
[3] 年珩, 庞博, 许国东, 等. 应对并补电网下DFIG系统高频谐振的宽频阻抗重塑策略[J]. 电力系统自动化, 2018, 42(18): 48-56.
NIAN H, PANG B, XU G D, et al.Reshaping strategy of wide frequency impedance for DFIG system to suppress high frequency resonance under parallel compensation grid[J]. Automation of electric power systems, 2018, 42(18): 48-56.
[4] CHI Y N, TANG B J, HU J B, et al.Overview of mechanism and mitigation measures on multi-frequency oscillation caused by large-scale integration of wind power[J]. CSEE journal of power and energy systems, 2019, 5(4): 433-443.
[5] 刘其辉, 田若菡, 贾瑞媛, 等. 基于模糊控制的双馈风电机组次同步振荡自适应抑制策略[J]. 太阳能学报, 2023, 44(7): 392-401.
LIU Q H, TIAN R H, JIA R Y, et al.Adaptive subsynchronous oscillation suppression strategy of double-fed wind power generator based on fuzzy control[J]. Acta energiae solaris sinica, 2023, 44(7): 392-401.
[6] 徐韵扬. 振荡频率耦合下风电机组的阻抗建模与并网稳定性分析[D]. 杭州: 浙江大学, 2021.
XU Y Y.Impedance modeling and stability analysis of the grid-connected wind turbine system under frequency-coupled oscillations[D]. Hangzhou: Zhejiang University, 2021.
[7] FAN L L, MIAO Z X.Nyquist-stability-criterion-based SSR explanation for type-3 wind generators[J]. IEEE transactions on energy conversion, 2012, 27(3): 807-809.
[8] MIAO Z X.Impedance-model-based SSR analysis for type 3 wind generator and series-compensated network[J]. IEEE transactions on energy conversion, 2012, 27(4): 984-991.
[9] SONG Y P, WANG X F, BLAABJERG F.Impedance-based high-frequency resonance analysis of DFIG system in weak grids[J]. IEEE transactions on power electronics, 2017, 32(5): 3536-3548.
[10] PANG B, NIAN H, XU Y Y.Mechanism analysis and damping method for high frequency resonance between VSC-HVDC and the wind farm[J]. IEEE transactions on energy conversion, 2021, 36(2): 984-994.
[11] 刘其辉, 董楚然, 于一鸣. 双馈风电并网系统高频谐振机理及抑制策略[J]. 电力自动化设备, 2020, 40(9): 163-169.
LIU Q H, DONG C R, YU Y M.High frequency resonance mechanism and suppression strategy of doubly-fed wind power grid-connected system[J]. Electric power automation equipment, 2020, 40(9): 163-169.
[12] 甘繁欣, 郭春义, 程浩, 等. 双馈风电场等值阻抗模型在高频振荡研究中的适用性分析与评价[J]. 中国电机工程学报, 2023, 43(19): 7497-7508.
GAN F X, GUO C Y, CHENG H, et al.Analysis and evaluation of the applicability of doubly-fed wind farm equivalent impedance model in high frequency resonance research[J]. Proceedings of the CSEE, 2023, 43(19): 7497-7508.
[13] WANG X F, HARNEFORS L, BLAABJERG F.Unified impedance model of grid-connected voltage-source converters[J]. IEEE transactions on power electronics, 2018, 33(2): 1775-1787.
[14] 熊小玲, 罗博晨, 刘京波, 等. 计及SVG的双馈风电场高频阻抗建模及振荡分析[J]. 电网技术, 2023, 47(7): 2905-2915.
XIONG X L, LUO B C, LIU J B, et al.High frequency impedance modeling and oscillation analysis of DFIG-based station considering SVG[J]. Power system technology, 2023, 47(7): 2905-2915.
[15] WEN B, BOROYEVICH D, BURGOS R, et al.Analysis of D-Q small-signal impedance of grid-tied inverters[J]. IEEE transactions on power electronics, 2016, 31(1): 675-687.
[16] 张学广, 马彦, 王天一, 等. 弱电网下双馈发电机输入导纳建模及稳定性分析[J]. 中国电机工程学报, 2017, 37(5): 1507-1515.
ZHANG X G, MA Y, WANG T Y, et al.Input admittance modeling and stability analysis of DFIG under weak grid condition[J]. Proceedings of the CSEE, 2017, 37(5): 1507-1515.
[17] SUN K, YAO W, FANG J K, et al.Impedance modeling and stability analysis of grid-connected DFIG-based wind farm with a VSC-HVDC[J]. IEEE journal of emerging and selected topics in power electronics, 2020, 8(2): 1375-1390.
[18] 张学广, 方冉, 马彦, 等. 弱电网情况下双馈风电机组改进虚拟感抗控制方法[J]. 电力系统自动化, 2018, 42(18): 33-40, 156.
ZHANG X G, FANG R, MA Y, et al.Control method of improved virtual inductance for DFIG based wind turbine under weak grid condition[J]. Automation of electric power systems, 2018, 42(18): 33-40, 156.
[19] 朱林, 钟丹婷, 王贝, 等. 含转子侧控制器的双馈风机建模与次同步振荡机理分析[J]. 电力系统自动化, 2021, 45(13): 40-48.
ZHU L, ZHONG D T, WANG B, et al.Modeling of doubly-fed wind turbine with rotor-side converter control and mechanism analysis of subsynchronous oscillation[J]. Automation of electric power systems, 2021, 45(13): 40-48.
[20] CHEN X J, LIU Z G.Impedance modeling and stability analysis of the converters in a double-fed induction generator (DFIG)-based system[J]. Energies, 2019, 12(13): 2500.
[21] 陈新, 王赟程, 龚春英, 等. 采用阻抗分析方法的并网逆变器稳定性研究综述[J]. 中国电机工程学报, 2018, 38(7): 2082-2094
CHEN X, WANG Y C, GONG C Y, et al.Overview of stability research for grid-connected inverters based on impedance analysis method[J]. Proceedings of the CSEE, 2018, 38(7): 2082-2094.
[22] 王天一. 基于阻抗分析法的双馈风力发电机系统稳定性研究[D]. 哈尔滨: 哈尔滨工业大学, 2017.
WANG T Y.Impedance-based stability research of DFIGsystem[D]. Harbin: Harbin Institute of Technology, 2017.
[23] WEN B, DONG D, BOROYEVICH D, et al.Impedance-based analysis of grid-synchronization stability for three-phase paralleled converters[J]. IEEE transactions on power electronics, 2016, 31(1): 26-38.
[24] 李辉, 王坤, 胡玉, 等. 双馈风电系统虚拟同步控制的阻抗建模及稳定性分析[J]. 中国电机工程学报, 2019, 39(12): 3434-3442.
LI H, WANG K, HU Y, et al.Impedance modeling and stability analysis of virtual synchronous control based on doubly-fed wind generation systems[J]. Proceedings of the CSEE, 2019, 39(12): 3434-3442.
[25] 杨超然, 宫泽旭, 洪敏, 等. 外环动态影响下变流器广义阻抗判据的适用性分析[J]. 中国电机工程学报, 2021, 41(9): 3012-3023.
YANG C R, GONG Z X, HONG M, et al.Applicability analysis of the generalized-impedance stability criterion for converters considering the outer-loop dynamics[J]. Proceedings of the CSEE, 2021, 41(9): 3012-3023.
[26] RYGG A, MOLINAS M, ZHANG C, et al.A modified sequence-domain impedance definition and its equivalence to the dq-domain impedance definition for the stability analysis of AC power electronic systems[J]. IEEE journal of emerging and selected topics in power electronics, 2016, 4(4): 1383-1396.
PDF(2506 KB)

Accesses

Citation

Detail

Sections
Recommended

/